4000 Series Local Pressure Controller

  • Repeatability: 0.5% of sensing element range
  • Deadband: 0.1% of output span
  • Differential Gap: 15-100% of sensing element range
  • Output Signal Range: 3-15 PSIG (0.21-1.03 BARG) or 6-30 PSIG (0.41-2.07 BARG)
  • Standard Temperature Limitations: -40°F to 160°F (-40°C to 71°C) 

More Details

4000 Series pressure controllers have two modes of operation: Proportional Only & Proportional + Reset. Control action is field reversible between direct acting and reverse acting. These controllers meet or exceed EPA emission standards, with standard controllers NACE ready with stainless steel parts.

Overview

 

4000 Series Local Pressure Controller

MODEL DESCRIPTION
   
4000 Proportional Only Controller
   
4010 Proportional-Plus-Reset Controller
   
4020 Bellows Sensing Controller
   
4030 Differential Gap Controller

Print

|

Back to Top

BOURDON TUBE PRESSURES AND MATERIALS
PRESSURE RANGES MAXIMUM ALLOWABLE STATIC PRESSURE LIMIT MATERIALS
PSIG BARG PSIG BARG
0 - 30 0 - 2.07 30 2.07 S31600
0 - 60 0 - 4.14 60 4.14 S31600
0 - 100 0 - 6.89 100 6.89 S31600
0 - 200 0 - 13.79 200 13.79 S31600
0 - 300 0 - 20.68 300 20.68 S31600
0 - 600 0 - 41.37 600 41.37 S31600*
0 - 1,000 0 - 68.95 1,000 68.95 S31600*
0 - 1,500 0 - 103.42 1,500 103.42 S31600*
0 - 3,000 0 - 206.84 3,000 206.84 S31600
0 - 5,000 0 - 344.74 5,000 344.74 S31600
 NOTES: * AVAILABLE IN N05500 (OTHER MATERIALS AND RANGES ARE SPECIAL ORDER).
SUPPLY PRESSURE REQUIREMENTS
OUTPUT SIGNAL RANGE
THROTTLING (ON/OFF)
NORMAL OPERATING SUPPLY PRESSURE (1) MAXIMUM ALLOWABLE SUPPLY PRESSURE TO PREVENT INTERNAL PART DAMAGE STEADY-STATE AIR CONSUMPTION
SCFH (STANDARD CUBIC FEET PER HOUR)
PSIG BARG PSIG BARG PSIG BARG PROPORTIONAL BAND
 SET TO 5
PROPORTIONAL BAND
SET TO 0 OR 10
0-15 (0-20) 0.21-1.03 (0-1.03) 20 1.38 40 2.76 MINIMUM 10
MAXIMUM 34
MINIMUM 2
MAXIMUM 30
6-30 (0-35) 0.41-2.07 (0-2.41) 35 2.41 40 2.76 MINIMUM 10
MAXIMUM 34
MINIMUM 5
MAXIMUM 6
NOTES: (1) CONTROL MAY BE DEGRADED IF THIS PRESSURE IS EXCEEDED.

Printable view

BOURDON TUBE PRESSURES AND MATERIALS
PRESSURE RANGES MAXIMUM ALLOWABLE STATIC PRESSURE LIMIT MATERIALS
PSIG BARG PSIG BARG
0 - 30 0 - 2.07 30 2.07 S31600
0 - 60 0 - 4.14 60 4.14 S31600
0 - 100 0 - 6.89 100 6.89 S31600
0 - 200 0 - 13.79 200 13.79 S31600
0 - 300 0 - 20.68 300 20.68 S31600
0 - 600 0 - 41.37 600 41.37 S31600*
0 - 1,000 0 - 68.95 1,000 68.95 S31600*
0 - 1,500 0 - 103.42 1,500 103.42 S31600*
0 - 3,000 0 - 206.84 3,000 206.84 S31600
0 - 5,000 0 - 344.74 5,000 344.74 S31600
 NOTES: * AVAILABLE IN N05500 (OTHER MATERIALS AND RANGES ARE SPECIAL ORDER).
SUPPLY PRESSURE REQUIREMENTS
OUTPUT SIGNAL RANGE
THROTTLING (ON/OFF)
NORMAL OPERATING SUPPLY PRESSURE (1) MAXIMUM ALLOWABLE SUPPLY PRESSURE TO PREVENT INTERNAL PART DAMAGE OUTPUT SIGNAL STEADY-STATE AIR CONSUMPTION (2)
SCFH (STANDARD CUBIC FEET PER HOUR)
PSIG BARG PSIG BARG PSIG BARG PSIG BARG
3-15 (0-20) 0.21-1.03 (0-1.38) 20 1.38 40 2.76 0 0 1.6
5 0.34 1.5
10 0.69 1.4
20 1.38 0.3
6-30 (0-35) 0.41-2.07 (0-2.41) 35 2.41 40 2.76 0 0 2.6
5 0.34 2.6
10 0.69 2.6
20 1.38 2.6
30 2.07 2.5
35 2.41 0.3
NOTES: (1) CONTROL MAY BE DEGRADED IF THIS PRESSURE IS EXCEEDED.
(2) SCFH: STANDARD CUBIC FEET PER HOUR = FT3/HR. @ 60°F AND 14.7 PSIG. AIR FLOW RATE INDICATED, FOR NATURAL GAS FLOW RATE - MULTIPLY BY 1.29.